Abstract
In this study, the application of S-transform with a frequency-dependent window is proposed for distinguishing internal incipient faults in transformers. The S-transform is applied to the recorded input current waveforms during the impulse test. Then, time-frequency contours of the S matrix are plotted and a suggested index is computed, accordingly. Faulty and healthy windings can be discriminated using time-frequency contours and proposed decision index. A 66-kV/25-MVA interleaved transformer winding is modelled in a MATLAB environment, also an arc discharge model is used and the effectiveness of the proposed method is studied. Laboratory tests are performed on this transformer winding and the performance of the method in noisy environments is investigated. According to the laboratory test and simulation results, it can be said that the suggested S-transform-based method is capable of detecting incipient faults conveniently.
Keywords
arcs (electric); fault diagnosis; impulse testing; matrix algebra; power transformer testing; time-frequency analysis; transformer windings; MATLAB environment; S matrix energy; S-transform-based method; apparent power 25 MVA; arc discharge model; frequency-dependent window; impulse test; interleaved transformer winding; internal incipient fault characterisation; noisy environment; recorded input current waveform; standard deviation; time-frequency contour; transformer fault; voltage 66 kV;
fLanguage
English
Journal_Title
Electric Power Applications, IET
Publisher
iet
ISSN
1751-8660
Type
jour
DOI
10.1049/iet-epa.2011.0257
Filename
6183687
Link To Document