• DocumentCode
    1498219
  • Title

    Synchronisation methods for grid-connected voltage source converters

  • Author

    Svensson, J.

  • Author_Institution
    Dept. of Electr. Power Eng., Chalmers Univ. of Technol., Goteborg, Sweden
  • Volume
    148
  • Issue
    3
  • fYear
    2001
  • fDate
    5/1/2001 12:00:00 AM
  • Firstpage
    229
  • Lastpage
    235
  • Abstract
    Four different synchronisation methods for a voltage source converter connected to a three-phase grid are investigated. The methods are adapted for use in a digital controller. The performance of the synchronisation methods is studied by response characteristics of phase-shift steps, frequency steps and low-frequency grid voltage harmonics. The low-pass filtering method can be used only if the frequency of the grid is constant and phase jumps do nor occur. If phase jumps occur, the novel space vector filtering method is recommended. The extended space vector filtering method is adapted to handle frequency variations and is also preferred if fast frequency variations occur. This method even has a higher performance than the extended Kalman filter method, in spite of the large number of calculations that must be performed
  • Keywords
    Kalman filters; filtering theory; harmonic distortion; power convertors; power system harmonics; synchronisation; extended Kalman filter method; frequency steps; grid-connected voltage source converters; low-frequency grid voltage harmonics; low-pass filtering method; phase jumps; phase-shift steps; response characteristics; space vector filtering method; synchronisation methods; three-phase power grid;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings-
  • Publisher
    iet
  • ISSN
    1350-2360
  • Type

    jour

  • DOI
    10.1049/ip-gtd:20010101
  • Filename
    926422