DocumentCode
1498594
Title
Controller action and control of a 330 kVA synchronous generator with a superconducting excitation winding
Author
Bischof, H. ; Groter, H.-P. ; Lorenzen, H.W.
Author_Institution
Tech. Univ. of Munchen, West Germany
Volume
25
Issue
2
fYear
1989
fDate
3/1/1989 12:00:00 AM
Firstpage
1795
Lastpage
1798
Abstract
Theoretical and experimental investigations were conducted during the last two years on the control of a 330-kVA synchronous generator with a superconducting field winding. The generator is connected either to the mains or to an island network. The superconducting field winding of the two-pole external pole synchronous generator is cooled indirectly by supercritical helium in a closed cooling circuit. The machine is controlled digitally by microcomputers at grid or island operation. A summary is given of test results on controlled generator operation (load decrease, variation of active and reactive power). Measured values are compared to the values gained from simulation are discussed
Keywords
superconducting machines; synchronous generators; 2 y; 330 kVA; active power control; closed cooling circuit; controlled generator operation; controller action; experimental investigations; grid operation; island network operation; load decrease; microcomputer control; reactive power control; superconducting excitation winding; superconducting field winding; supercritical He cooling; synchronous generator; test results; two-pole external pole synchronous generator; Circuit testing; Cooling; Digital control; Gain measurement; Helium; Microcomputers; Power generation; Reactive power control; Superconducting transmission lines; Synchronous generators;
fLanguage
English
Journal_Title
Magnetics, IEEE Transactions on
Publisher
ieee
ISSN
0018-9464
Type
jour
DOI
10.1109/20.92650
Filename
92650
Link To Document