DocumentCode
1500061
Title
Anode and cathode arc root movement during contact opening at high current
Author
McBride, John W. ; Jeffery, Peter A.
Author_Institution
Dept. of Mech. & Electr. Eng., Southampton Univ., UK
Volume
22
Issue
1
fYear
1999
fDate
3/1/1999 12:00:00 AM
Firstpage
38
Lastpage
46
Abstract
This paper presents experimental research into the behavior of short circuit break arcs ignited between opening contacts. The investigation is applied to arc chamber geometries commonly used in miniature circuit breakers (MCB). The movement of the anode and cathode roots are individually plotted from optical data, allowing the relative motion to be compared. The effect of a range of MCB configurations on the arc root motion has been investigated. The experiment was configured so that the fixed contact was always the cathode. The results show that the two are roots do not move away from the contact region simultaneously. Often the cathode root moved off the fixed contact and away from the contact region before the anode root commutated from the moving contact. The delay in anode root commutation leads to a delayed cathode root movement. These events are explained in terms of arc root emission processes
Keywords
circuit breakers; circuit-breaking arcs; commutation; current limiters; electrical contacts; arc root motion; commutation; high current loading; miniature circuit breaker; opening contact; short circuit break arc; Anodes; Cathodes; Circuit breakers; Circuit faults; Circuit testing; Current density; Delay; Inorganic materials; Thermionic emission; Voltage;
fLanguage
English
Journal_Title
Components and Packaging Technologies, IEEE Transactions on
Publisher
ieee
ISSN
1521-3331
Type
jour
DOI
10.1109/6144.759351
Filename
759351
Link To Document