DocumentCode :
1511159
Title :
Ground Fault Temporary Overvoltages in MV Networks: Evaluation and Experimental Tests
Author :
Cerretti, Alberto ; Gatta, Fabio Massimo ; Geri, Alberto ; Lauria, Stefano ; Maccioni, Marco ; Valtorta, Giovanni
Author_Institution :
ENEL Distribuzione S.p.A., Rome, Italy
Volume :
27
Issue :
3
fYear :
2012
fDate :
7/1/2012 12:00:00 AM
Firstpage :
1592
Lastpage :
1600
Abstract :
Single-phase-to-ground faults may cause substantial temporary overvoltages (TOVs) in large radial medium-voltage networks with isolated neutral, even over 3-p.u. phase to ground. Resonant neutral earthing limits these overvoltages to 1.8 p.u. but credible earthing apparatus failures might trigger TOVs up to 2.4 p.u. This paper presents the ground fault study of an Italian 20-kV ENEL Distribuzione network. Analytical evaluations in a wide parametric range of neutral earthing arrangements, include isolated neutral and ENEL resonant earthing with parallel resistance, as evidence of 2.4-p.u. TOVs with isolated neutral, 1.8 p.u. with resonant earthing, and more than 2.0 p.u. with partial compensation. Recordings of ground faults staged in the same network are presented, showing excellent agreement between analytical predictions and experimental test. The tests confirm TOVs of more than 2.3 p.u. with isolated neutral, sometimes evolving into cross-country faults (possibly explaining unforeseen cable fault rates), and the effectiveness of the ENEL neutral earthing practices in suppressing these TOVs.
Keywords :
earthing; overvoltage protection; power distribution faults; power distribution protection; Italian ENEL Distribuzione network; cross-country faults; ground fault temporary overvoltages; large radial medium-voltage networks; resonant neutral earthing; single-phase-to-ground faults; voltage 20 kV; Circuit faults; Coils; Fault currents; Grounding; Impedance; Resistance; Surges; Earth fault; isolated neutral; resonant neutral earthing; temporary overvoltages;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2012.2192456
Filename :
6196195
Link To Document :
بازگشت