DocumentCode :
1512856
Title :
Experience with PDA diagnostic testing on hydraulic generators
Author :
Lyles, J.F. ; Stone, G.C. ; Kurtz, M.
Author_Institution :
Ontario Hydro, Ont., Canada
Volume :
3
Issue :
4
fYear :
1988
fDate :
12/1/1988 12:00:00 AM
Firstpage :
824
Lastpage :
832
Abstract :
This paper describes the capability of the partial discharge analyzer (PDA) test to distinguish between the various operative mechanisms of stator winding insulation deterioration (if any). The ability to distinguish between the various mechanisms yields significant benefits in scheduling priorities for inspection, repairs, and possible locations of deterioration. Two normalized quantity number charts are presented: one for polyester and epoxy stator insulation systems, and one for asphalt-mica and mica folium stator insulation systems. Their stated insulation damage relationships are based on Ontario Hydro´s operating experience over the past 15 years
Keywords :
insulation testing; machine insulation; machine testing; stators; PDA diagnostic testing; asphalt-mica insulation; epoxy insulation; hydraulic generators; inspection; mica folium insulation; normalized quantity number charts; partial discharge analyzer; polyester insulation; repairs; stator winding insulation deterioration; Bonding; Building materials; Coils; Condition monitoring; Copper; Delamination; Inspection; Insulation testing; Partial discharges; Stator windings;
fLanguage :
English
Journal_Title :
Energy Conversion, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8969
Type :
jour
DOI :
10.1109/60.9358
Filename :
9358
Link To Document :