DocumentCode
1513979
Title
Assessment of ROCPAD Relay for Islanding Detection in Distributed Generation
Author
Samui, Ankita ; Samantaray, S.R.
Author_Institution
Sch. of Electr. Sci., Indian Inst. of Technol. Bhubaneswar, Bhubaneswar, India
Volume
2
Issue
2
fYear
2011
fDate
6/1/2011 12:00:00 AM
Firstpage
391
Lastpage
398
Abstract
The paper presents a new approach for islanding detection in distributed generation (DG) using rate of change of phase angle difference (ROCPAD). The process starts with retrieving the voltage and current signals at the DG end and estimating the phasors (amplitude, phase, and frequency) using synchronous transformation based algorithm. The next step is to compute the phase angle difference and the ROCPAD for registering islanding detection. The proposed algorithm is compared with the widely used rate of change of frequency relays (ROCOF) and found working effectively in the situations where ROCOF fails. The proposed ROCPAD relay is tested on standard microgrid structures with possible variations in operating parameters and the results indicate that the ROCPAD relay can reliably detect islanding conditions in large microgrids.
Keywords
distributed power generation; ROCPAD relay; distributed generation; islanding detection; micro-grid structure; rate of change of frequency relay; rate of change of phase angle difference; synchronous transformation; Circuit breakers; Distributed power generation; Estimation; Frequency estimation; Power systems; Relays; Switches; Active power imbalance; distributed generation (DG); microgrid; rate of change of frequency (ROCOF); rate of change of phase angle difference (ROCPAD);
fLanguage
English
Journal_Title
Smart Grid, IEEE Transactions on
Publisher
ieee
ISSN
1949-3053
Type
jour
DOI
10.1109/TSG.2011.2125804
Filename
5765717
Link To Document