• DocumentCode
    1513979
  • Title

    Assessment of ROCPAD Relay for Islanding Detection in Distributed Generation

  • Author

    Samui, Ankita ; Samantaray, S.R.

  • Author_Institution
    Sch. of Electr. Sci., Indian Inst. of Technol. Bhubaneswar, Bhubaneswar, India
  • Volume
    2
  • Issue
    2
  • fYear
    2011
  • fDate
    6/1/2011 12:00:00 AM
  • Firstpage
    391
  • Lastpage
    398
  • Abstract
    The paper presents a new approach for islanding detection in distributed generation (DG) using rate of change of phase angle difference (ROCPAD). The process starts with retrieving the voltage and current signals at the DG end and estimating the phasors (amplitude, phase, and frequency) using synchronous transformation based algorithm. The next step is to compute the phase angle difference and the ROCPAD for registering islanding detection. The proposed algorithm is compared with the widely used rate of change of frequency relays (ROCOF) and found working effectively in the situations where ROCOF fails. The proposed ROCPAD relay is tested on standard microgrid structures with possible variations in operating parameters and the results indicate that the ROCPAD relay can reliably detect islanding conditions in large microgrids.
  • Keywords
    distributed power generation; ROCPAD relay; distributed generation; islanding detection; micro-grid structure; rate of change of frequency relay; rate of change of phase angle difference; synchronous transformation; Circuit breakers; Distributed power generation; Estimation; Frequency estimation; Power systems; Relays; Switches; Active power imbalance; distributed generation (DG); microgrid; rate of change of frequency (ROCOF); rate of change of phase angle difference (ROCPAD);
  • fLanguage
    English
  • Journal_Title
    Smart Grid, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1949-3053
  • Type

    jour

  • DOI
    10.1109/TSG.2011.2125804
  • Filename
    5765717