Title :
The application of commitment utilization factor (CUF) to thermal unit commitment
Author_Institution :
Oklahoma Univ., Norman, OK, USA
fDate :
5/1/1991 12:00:00 AM
Abstract :
A new approach is presented for determining the priority order for thermal unit commitment. In this approach, a new index CUF (commitment utilization factor) is used in conjunction with the classical economic index AFLC (average full-load cost) to determine the priority commitment order. The proposed approach has been found to be very effective because the resulting priority commitment orders are consistently better, whenever possible, than those determined by the AFLC index alone. This approach can be easily implemented as an add-on module to an existing priority-order-based unit commitment model. The addition can significantly improve the performance of this priority-order-based model without noticeable penalty in the computational requirements. A midwestern utility system is used to illustrate the proposed approach
Keywords :
electricity supply industry; load dispatching; thermal power stations; average full-load cost; commitment utilization factor; economic index; midwestern utility system; priority-order-based model; thermal unit commitment; Cost function; Dynamic programming; Environmental economics; Fuel economy; Power & Energy Society; Power engineering computing; Power generation economics; Power system modeling; Power systems; Thermal factors;
Journal_Title :
Power Systems, IEEE Transactions on