• DocumentCode
    1517492
  • Title

    A statistical method of assessing the safety of gaps between flanges of flameproof electrical apparatus

  • Author

    Bruce, C.E.R. ; Johnson, N.L.

  • Volume
    95
  • Issue
    43
  • fYear
    1948
  • fDate
    2/1/1948 12:00:00 AM
  • Firstpage
    49
  • Lastpage
    58
  • Abstract
    The paper gives the results of the authors´ statistical analysis of tests made by the Safety in Mines Research Board (S.M.R.B.) to establish conditions of flameproofness of flange gaps for electrical gear for use in hazardous atmospheres. The chance of occurrence of an ignition of an external explosive atmosphere when an explosion occurs inside the flanged vessel, is found to increase approximately linearly with the size of the gap at the flanges. From a study of this variation of chance of ignition with flange gap, it has been possible to determine a gap which is safe within a certain approximately known risk, both for the case of a linear increase of chance with gap, and for the more accurate empirical law of variation of chance with gap deduced from the experimental data. Thus values of the statistical maximum safe gap are given for a number of hazardous atmospheres; these are such that, so far as can be determined, there is only a chance of the order of 1 in 1012 that the true maximum safe gap is actually less than the value given. These data afforded a basis for the determination of the maximum permissible gaps given in B.S. 229: 1946.
  • Keywords
    electrical engineering equipment;
  • fLanguage
    English
  • Journal_Title
    Electrical Engineers - Part II: Power Engineering, Journal of the Institution of
  • Publisher
    iet
  • Type

    jour

  • DOI
    10.1049/ji-2.1948.0008
  • Filename
    5296694