Title :
A method for calibration of partial discharge calibrators
Author :
Gunnarsson, Ove ; Bergman, Anders ; Rydler, Karl-Erik
Author_Institution :
Nat. Testing & Res. Inst., Boras, Sweden
fDate :
4/1/1999 12:00:00 AM
Abstract :
A method for calibration of partial discharge calibrators has been developed based on passive integration of the induced charge. The voltage over a known capacitor is measured by a calibrated digital sampling voltmeter and the charge is calculated as the voltage multiplied by the capacitance. The best achieved uncertainty is ±2% with a coverage factor k=2
Keywords :
calibration; high-voltage techniques; measurement uncertainty; partial discharge measurement; HV techniques; calibration method; charge measurement; digital sampling voltmeter; impulse charge; induced charge; partial discharge calibrators; passive integration; pulse measurements; uncertainty; Calibration; Capacitance measurement; Capacitors; Charge measurement; Current measurement; Partial discharge measurement; Partial discharges; Sampling methods; Voltage; Voltmeters;
Journal_Title :