DocumentCode :
1521426
Title :
An improved transmission-line model of grounding system
Author :
Liu, Yaqing ; Zitnik, Mihael ; Thottappillil, Rajeev
Author_Institution :
Angstrom Lab., Uppsala Univ., Sweden
Volume :
43
Issue :
3
fYear :
2001
fDate :
8/1/2001 12:00:00 AM
Firstpage :
348
Lastpage :
355
Abstract :
This paper presents a time-domain transmission line model of grounding system, which includes the mutual electromagnetic coupling between the parts of the grounding structure and the influence of air-earth interface. The model can be used to simulate the transient behavior of the grounding system under lightning strike. The simulation results are in good agreement with that of the model based on the solution of full Maxwell´s equations. The influence of different parameters, such as the soil relative permittivity ετ, the soil resistivity ρ, and the conductivity and diameter of the conductor, on the transient voltage distribution of the grounding system is investigated. It shows that, among the parameters investigated here, the soil resistivity is the most important parameter that affects the transient response of bare buried conductors. The soil permittivity has very little influence on the transient response of the grounding system when the grounding system is buried in the soil with low resistivity, but have moderate influence in the soil with extremely high resistivity. The conductivity of the conductor and skin effect have practically no influence on the peak transient voltage of the grounding system. Increase in conductor diameter tends to decrease the peak transient voltage. The model presented in this paper is simple, but sufficiently accurate and can be used easily in engineering practice. Since the model is in the time domain, it could be easily coupled to the other time-domain models of nonlinear surge-protection components
Keywords :
earthing; lightning protection; power system protection; soil; time-domain analysis; transient response; transmission line theory; air-earth interface; conductor conductivity; conductor diameter; grounding structure; grounding system; lightning strike; mutual electromagnetic coupling; nonlinear surge-protection components; peak transient voltage; skin effect; soil permittivity; soil relative permittivity; soil resistivity; time-domain transmission line model improvement; transient behavior; transient response; transient voltage distribution; Conductivity; Conductors; Grounding; Permittivity; Power system transients; Soil; Time domain analysis; Transient response; Transmission lines; Voltage;
fLanguage :
English
Journal_Title :
Electromagnetic Compatibility, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9375
Type :
jour
DOI :
10.1109/15.942606
Filename :
942606
Link To Document :