DocumentCode :
15249
Title :
Fault Current Contribution of Medium Voltage Inverter and Doubly-Fed Induction-Machine-Based Flywheel Energy Storage System
Author :
Abdel-khalik, A.S. ; Elserougi, Ahmed Abbas ; Massoud, Ahmed Mohamed ; Ahmed, Shehab
Author_Institution :
Dept. of Electr. Eng., Alexandria Univ., Alexandria, Egypt
Volume :
4
Issue :
1
fYear :
2013
fDate :
Jan. 2013
Firstpage :
58
Lastpage :
67
Abstract :
One of the main concerns with inverter-based distributed generation (IBDG) is its negligible fault current contribution compared to synchronous generators. IBDG hardly affects fault current level, which shadows conventional protection schemes especially with a high penetration of IBDGs at high power levels and/or in island operation mode. This paper proposes a solution for IBDG in a medium voltage distribution network that allows active and adjustable IBDG fault current contribution without violating the nonoverload nature of the inverters. This is achieved by introducing a flywheel energy storage system based on a doubly-fed induction machine (DFIM) in parallel with the IBDG. Normally, the flywheel system is dedicated to power leveling; however, during faults, the flywheel DFIM storage system (FW-DFIM) has the ability to supply an exponentially decaying current to the grid. The parallel combination of the IBDG and FW-DFIM as a distributed generation (DG) unit is capable of providing a response similar to that of synchronous generators during a fault, but with additional control capability. The simulated system shows the effectiveness of the DG unit for downstream faults where it is capable of providing sufficient fault current to trigger the distribution network´s protection devices when operating in island mode.
Keywords :
asynchronous machines; distributed power generation; fault currents; flywheels; invertors; power distribution faults; power distribution protection; power grids; FW-DFIM; IBDG; current decaying; distribution network protection schemes; doubly-fed induction-machine-based flywheel energy storage system; fault current contribution; inverter-based distributed generation; island operation mode; medium voltage distribution network; medium voltage inverter; power grid; power leveling; synchronous generator; Circuit faults; Fault currents; Inverters; Medium voltage; Reactive power; Rotors; Stators; Distributed generation (DG); doubly-fed induction machine (DFIM); fault current level; flywheel storage system; inverter;
fLanguage :
English
Journal_Title :
Sustainable Energy, IEEE Transactions on
Publisher :
ieee
ISSN :
1949-3029
Type :
jour
DOI :
10.1109/TSTE.2012.2198926
Filename :
6209458
Link To Document :
بازگشت