• DocumentCode
    1525095
  • Title

    Experience with an inverter-based dynamic voltage restorer

  • Author

    Woodley, N.H. ; Morgan, L. ; Sundaram, A.

  • Author_Institution
    Westinghouse Electr. Corp., Pittsburgh, PA, USA
  • Volume
    14
  • Issue
    3
  • fYear
    1999
  • fDate
    7/1/1999 12:00:00 AM
  • Firstpage
    1181
  • Lastpage
    1186
  • Abstract
    The installation of the world´s first dynamic voltage restorer (DVR) on a major US utility system to protect a critical customer plant load from power system voltage disturbances ushers in a new era of power quality problem solution on the utility side of the revenue billing meter. The prototype DVR built by Westinghouse for EPRI was installed in August, 1996 on the Duke Power Company (North Carolina) 12.47 kV system at an automated yarn manufacturing and weaving factory where it provides protection from disturbances coming from the utility distribution system that serves the plant. This paper describes the prototype DVR installation and presents early results from the demonstration project
  • Keywords
    DC-AC power convertors; industrial power systems; invertors; load (electric); power supply quality; power system faults; power system protection; power system restoration; textile industry; 12.47 kV; USA; commercial power systems; critical customer plant load; demonstration project; distribution system disturbance protection; electric utilities; power system voltage disturbances; yarn manufacturing factory; yarn weaving factory; Manufacturing automation; Power quality; Power system dynamics; Power system protection; Power system restoration; Production facilities; Prototypes; Voltage; Weaving; Yarn;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.772390
  • Filename
    772390