DocumentCode
1526371
Title
Thirty-Six Years of Service Experience with a National Population of Gas-Insulated Substations
Author
Istad, Maren ; Runde, Magne
Author_Institution
Dept. of Electr. Power Eng., Norwegian Univ. of Sci. & Technol., Trondheim, Norway
Volume
25
Issue
4
fYear
2010
Firstpage
2448
Lastpage
2454
Abstract
This paper shows the result of a failure survey including the entire population of gas-insulated substations in the Norwegian power transmission system. The survey comprises the complete service experience up to now-nearly 12000 circuit-breaker years. Information about 180 failures has been recorded during 36 years: 77 internal flashovers/arcing faults have occurred, four of which burned through the encapsulation and another six caused the pressure-relief devices to operate. No severe injuries have been recorded. The overall failure rates and their causes are comparable to the findings of other reliability surveys, although the occurrence of severe arcing faults appears to be clearly higher than noticed elsewhere. The 300-kV and 420-kV gas-insulated substations put into service around 1980 have a significant and negative influence on the overall failure rate, whereas a large number of 145-kV substations installed since the early 1990s have proven very reliable. Even though a large portion of the population is above or approaching the designed service life of 30 years, no significant aging problems could be revealed with a basis in the failure statistics.
Keywords
circuit-breaking arcs; flashover; gas insulated substations; power transmission faults; power transmission reliability; Norwegian power transmission system; arcing faults; circuit breaker; failure survey; gas insulated substations; internal flashovers; national population; reliability surveys; service experience; voltage 145 kV; voltage 300 kV; voltage 420 kV; Circuit faults; Databases; Encapsulation; Flashover; Geographic Information Systems; Injuries; Manufacturing; Power transmission; Statistics; Substations; Aging; end of life; failure analysis; gas-insulated substations (GIS); reliability; sulfur hexafluoride; switchgear;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2010.2050705
Filename
5497198