• DocumentCode
    1528779
  • Title

    Transient Earth Voltage Measurement in PD Detection of Artificial Defect Models in \\hbox {SF}_{6}

  • Author

    Ren, Ming ; Dong, Ming ; Ren, Zhong ; Peng, Hua-Dong ; Qiu, Ai-Ci

  • Author_Institution
    State Key Lab. of Electr. Insulation for Power Equip., Xi´´an Jiaotong Univ., Xi´´an, China
  • Volume
    40
  • Issue
    8
  • fYear
    2012
  • Firstpage
    2002
  • Lastpage
    2008
  • Abstract
    This paper mainly discussed the utilization of transient Earth voltage measurement (TEVM) in partial discharge (PD) detection of gas insulation switchgear. Four typical artificial defect models in SF6 such as spikes fixed on high voltage (HV) conductor, suspended metals, voids in dielectric, and metal particles on the surface of dielectric had been used as test objects in ac PD experiments with the aid of the synchronized PD signals sampled from a transient Earth voltage sensor, photomultiplier, Rogowski monitor, and PDCheck system. The measuring results of TEVM results, which included the phase distribution of PD, the relative amplitude, and the pulse number of different voltage thresholds, showed good consistency with three other methods and had better sensitivity of detection in spark or corona PD patterns. For further study, the frequency distributions of the three PD patterns were analyzed and discussed for understanding the different measurement sensitivities showed in different typical defects in SF6 . In addition, TEVM was applied to detect PD under oscillating impulse voltage. As an example, the needle-plane electrode with short gap was adopted under 613.2-kHz oscillating impulse, which showed the effectiveness in this kind of detection.
  • Keywords
    SF6 insulation; corona; electric sensing devices; gas insulated switchgear; partial discharge measurement; photomultipliers; sparks; transients; PD detection; PDCheck system; Rogowski monitor; SF6; TEVM; artificial defect model; corona PD pattern; frequency distribution; gas insulation switchgear; oscillating impulse voltage; partial discharge; phase distribution; photomultiplier; pulse number; relative amplitude; spark PD pattern; synchronized PD signal; transient Earth voltage sensor; transient earth voltage measurement; voltage threshold; Discharges; Metals; Needles; Partial discharges; Sulfur hexafluoride; Voltage measurement; Gas insulation switchgear (GIS); insulation defect; insulation diagnosis; partial discharge (PD); transient Earth voltage measurement (TEVM);
  • fLanguage
    English
  • Journal_Title
    Plasma Science, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-3813
  • Type

    jour

  • DOI
    10.1109/TPS.2012.2199135
  • Filename
    6209438