DocumentCode :
1531843
Title :
A survey of generator back-up protection practices: IEEE committee report
Author :
Rockefeller, G.D. ; Darlington, A.N. ; Elmore, W.A. ; Fernandez, R.J. ; Gil-Berlinches, J.R. ; Haas, R.W. ; Landoll, L.E. ; Marsh, W.J. ; Nail, G.R. ; Pierce, A.C. ; Wagner, C.L. ; Wright, L.S.
Volume :
5
Issue :
2
fYear :
1990
fDate :
4/1/1990 12:00:00 AM
Firstpage :
575
Lastpage :
584
Abstract :
The authors report on and analyze a survey of practices and experiences with time-delay back-up protection associated with unit-connected generators, predominantly rated 100 MVA and above. In addition, application and setting considerations are discussed. The survey covered large unit-connected installations, involving 47 respondents and 6698 unit-years of experience. Phase back-up, negative-sequence overcurrent, and high-side neutral overcurrent protection were considered. The majority of respondents were found to apply all three classes of back-up protection: phase, negative-sequence, and high-side neutral overcurrent
Keywords :
electric generators; machine protection; 100 MVA; generator back-up protection practices; high-side neutral overcurrent protection; negative-sequence overcurrent; phase back-up;