DocumentCode
1532313
Title
Adaptive ground fault protection schemes for turbogenerator based on third harmonic voltages
Author
Yin, X.G. ; Malik, O.P. ; Hope, G.S. ; Chen, D.S.
Author_Institution
Huazhong Univ. of Sci. & Technol., Wuhan, China
Volume
5
Issue
2
fYear
1990
fDate
4/1/1990 12:00:00 AM
Firstpage
595
Lastpage
603
Abstract
Equivalent circuits based on the actual connection of coil-groups of generators are used to study the characteristics of various generator stator ground fault protection schemes presented in the literature. The evaluation and the comparison of the characteristics of those schemes are given by means of protection coverage-critical resistance curves. Although these schemes are successful in practice, they suffer the disadvantage of low sensitivity, which is strongly related to generator operating conditions. To overcome this disadvantage, two adaptive stator ground fault protection schemes based on digital techniques are developed. Compared to conventional third-harmonic voltage schemes, they can automatically track the change of generator operating conditions before a ground fault occurs. Test results from a digital simulation show that they can keep high sensitivity during all operating conditions
Keywords
fault currents; harmonics; machine protection; synchronous generators; turbogenerators; adaptive stator ground fault protection schemes; coil-groups; digital techniques; stator ground fault protection schemes; third harmonic voltages; turbogenerator; Admittance; Capacitance; Character generation; Circuit faults; Equivalent circuits; Magnetic field measurement; Protection; Stator windings; Turbogenerators; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.53061
Filename
53061
Link To Document