Basic aspects of applying SVC´s to series-compensated AC transmission lines
Author :
Larsen, Einar V. ; Baker, Daniel H. ; Imece, Ali F. ; Gerin-Lajoie, Luc ; Scott, Guy
Author_Institution :
GE Ind. & Utility Sales, Schenectady, NY, USA
Volume :
5
Issue :
3
fYear :
1990
fDate :
7/1/1990 12:00:00 AM
Firstpage :
1466
Lastpage :
1473
Abstract :
Basic information is presented on SVC (static VAR compensator) interactions with series-compensated transmission lines. A potential exists for adverse interactions which are different from the type seen in AC systems without series compensation. Secure operation can be attained by minor modifications to the SVC control system, but specific studies are suggested, at least for each different SVC control type. Such studies will impose added difficulty in the process of specifying, bid evaluation, and commissioning of SVC equipment. Objectives of procedures to simplify this process are stated
Keywords :
compensation; power transmission lines; reactive power; static VAr compensators; commissioning; control system; interactions; power factor; reactive power compensation; series-compensated AC transmission lines; static VAR compensator; Capacitance; Capacitors; Inductance; Inductors; Power transmission lines; Resonance; Resonant frequency; Shunt (electrical); Static VAr compensators; Transmission lines;