DocumentCode
1536195
Title
Testing of lattice towers for Ontario Hydro transmission line refurbishment program
Author
Krishnasamy, S.G. ; Senkiw, G.A. ; Havard, D.G. ; Pon, C.J. ; Tabatabai, M. ; Hathout, I. ; Radhakrishna, H.S. ; Tsang, R.H.K.
Author_Institution
Ontario Hydro, Toronto, Ont., Canada
Volume
5
Issue
3
fYear
1990
fDate
7/1/1990 12:00:00 AM
Firstpage
1474
Lastpage
1483
Abstract
As part of the ongoing transmission-line refurbishment study, three single-circuit, 115 kV, Kingston-type suspension towers on rock-anchor foundations were tested to failure. The types of loads applied to the towers were chosen to represent unbalanced loads due to broken skywire and conductor, heavy-ice, strong-wind and wind-on-ice loads. Selected tower members and foundations were instrumented to measure the member loads, tower deflections, and foundation movement during various stages of testing. The measured values were compared with the corresponding predicted values. The correlation between the predicted and actual tower-failure loads is good. The tower tests confirmed that there is reserve strength available for upgrading the conductor on this line. The measured tower member loads and functions loads correlated fairly satisfactorily with the corresponding calculated values. The rock-anchor foundation did not show any movement at all. The test towers, the tower loading schedule, instrumentation, and tower-testing procedures are described. Measured and predicted failure load are presented. Measured and predicted deflections at selected joints just prior to failure and loads on members just prior to failure are also included
Keywords
maintenance engineering; poles and towers; power overhead lines; testing; 115 kV; Canada; Kingston-type suspension towers; Ontario Hydro; conductor; failure; foundations; lattice towers; mechanical testing; power overhead lines; reliability; reserve strength; transmission line refurbishment; unbalanced loads; Circuit testing; Conductors; Distributed parameter circuits; Ice; Instruments; Lattices; Poles and towers; Power transmission lines; Transmission line measurements; Transmission lines;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.57991
Filename
57991
Link To Document