DocumentCode
1536503
Title
Energizing high and extra-high voltage lines during restoration
Author
Adibi, M.M. ; Alexander, R.W. ; Milanicz, D.P.
Author_Institution
IRD Corp., USA
Volume
14
Issue
3
fYear
1999
fDate
8/1/1999 12:00:00 AM
Firstpage
1121
Lastpage
1126
Abstract
In energizing power transmission lines, operators are often concerned with: the length of line to be energized; the adequacy of online generation; and the size of underlying load. There has been a need for a simple methodology to readily address these issues and provide guidelines for the safe operation of high voltage and extra-high voltage transmission lines. In this paper, a simple and approximate approach for evaluating sustained and transient voltages is presented. The sending- and receiving-end sustained and transient voltages are determined for energizing lines of different voltage levels and lengths, energized by different sizes of generators, and having different sizes of underlying loads
Keywords
load (electric); overvoltage; power system restoration; power system transients; power transmission lines; extra-high voltage power lines; high-voltage power lines; online generation adequacy; power system restoration; power transmission line energisation; sustained voltages; transient voltages; underlying load size; EMTP; Equations; Guidelines; Impedance; Power system modeling; Power system restoration; Power system transients; Power transmission lines; Samarium; Voltage control;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/59.780939