    A New Algorithm to Avoid Maloperation of Transformer Differential Protection in Substations With an Inner Bridge Connection

  • Author

    Zheng, T. ; Gu, J. ; Huang, S.F. ; Guo, F. ; Terzija, V.

  • Author_Institution
    State Key Lab. of Alternate Electr. Power Syst. with Renewable Energy Sources, North China Electr. Power Univ., Beijing, China
  • Volume
    27
  • Issue
    3
  • fYear
    2012
  • fDate
    7/1/2012 12:00:00 AM
  • Firstpage
    1178
  • Lastpage
    1185
  • Abstract
    In substations with an inner bridge connection, the two main transformers are generally connected in parallel. The differential protection of the transformer, under normal operating conditions, may maloperate when the other transformer is switching on through the bridge breaker after scheduled maintenance. This paper analyzes the factors that may lead to the maloperation of transformer differential protection and concludes that local transient saturation of the current transformer (CT) caused by the decaying dc component in the magnetizing inrush is the main cause of the maloperation of the transformer differential protection. By detecting the time difference between the instant of sudden changes occurring in the transformer wye-side current and the instant of the differential current increasing, a new algorithm based on the time differential method is proposed in this paper, which can prevent the maloperation of transformer differential protection in substations with an inner bridge connection. On the basis of detailed analysis and simulation work, the new algorithm is verified to be applicable under the conditions of sympathetic inrush and CT saturation.
  • Keywords
    current transformers; power system protection; substation protection; transformer protection; bridge breaker; current transformer; decaying dc component; inner bridge connection; local transient saturation; magnetizing inrush; normal operating conditions; scheduled maintenance; substations; sympathetic inrush; transformer differential protection; transformer wye-side current; Circuit faults; Current transformers; Fault currents; Saturation magnetization; Surge protection; Surges; Transient analysis; Current-transformer (CT) saturation; magnetizing inrush; sympathetic inrush; time difference; transformer differential protection;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2012.2192942
  • Filename
    6215003