    Earthing effects of coated underground cables with metallic shields bonded to earth electrodes

  • Author

    Nahman, J.

  • Author_Institution
    Faculty of Electr. Eng., Belegrade, Yugoslavia
  • Volume
    144
  • Issue
    1
  • fYear
    1997
  • fDate
    1/1/1997 12:00:00 AM
  • Firstpage
    26
  • Lastpage
    30
  • Abstract
    Relatively simple expressions are derived for assessing the earthing effects of coated MV underground power cables with metallic shields (protective conductors) connected to source, and consumers´ transformer substations´ earth electrodes including the transferred potentials and touch and step voltages. The analysis performed for typical sample cases has shown that such cables might substantially affect the earthing system performances of the source substation and the associated distribution network and that, therefore, they have to be adequately taken into account for a rational and safe earthing system design
  • Keywords
    underground cables; coated MV underground power cables; distribution network; earth electrodes; earthing effects; earthing system performance; metallic shields; step voltage; touch voltage; transferred potentials; transformer substation;