Title :
Design method of volt/turn for minimizing life cost of a superconducting transformer
Author :
Ise, T. ; Murakami, Y.
Author_Institution :
Dept. of Electr. Eng., Osaka Univ., Japan
fDate :
6/1/1999 12:00:00 AM
Abstract :
Many transformers using low Tc or high Tc superconductors have been built and tested, but it is still not clear how to design the volt/turn ratio property. This paper shows one design method, which minimizes total cost including initial cost and running cost. According to the results, the optimized volt/turn will be around 1 volt which is considerably lower than the volt/turn ratio of a conventional transformer of 10 to 20 volts.
Keywords :
life cycle costing; power transformers; superconducting transformers; transformer windings; 40 kVA; high Tc superconductors; initial cost; life cost minimisation; low Tc superconductors; running cost; superconducting transformer; volt/turn design method; Cost function; Design engineering; Design methodology; High temperature superconductors; Iron; Magnetic flux; Superconducting filaments and wires; Superconducting magnets; Testing; Transformer cores;
Journal_Title :
Applied Superconductivity, IEEE Transactions on