Abstract
Very fast transient overvoltages generated in gas-insulated switchgear could cause a voltage oscillation inside the connected transformer. A practical method to calculate the high-frequency transients in the transformer winding is developed based on multiconductor transmission-line theory. Resonance characteristics of a transformer are assessed using the inductance matrix obtainable from its winding geometry. Applicability to transients of frequencies up to several megahertz is checked in a model transformer and an actual 500 kV transformer. The calculated interturn voltage waveforms are in particularly good agreement with experiment
Keywords
inductance; multiconductor transmission lines; oscillations; power transformers; resonance; transformer windings; transient analysis; transmission line theory; 500 kV; gas-insulated switchgear; inductance matrix; interturn voltage waveforms; multiconductor transmission-line theory; power transformers; resonance characteristics; transformer winding; very fast transient overvoltages; very fast transients analysis; voltage oscillation; winding geometry;