DocumentCode :
1543950
Title :
Combined switching harmonics from multiple grid-connected single-phase inverters
Author :
Infield, D.G.
Author_Institution :
Dept. of Electron. & Electr. Eng., Loughborough Univ.
Volume :
148
Issue :
5
fYear :
2001
fDate :
9/1/2001 12:00:00 AM
Firstpage :
427
Lastpage :
430
Abstract :
The paper is concerned with the manner in which random phase harmonics, and in particular switching harmonics, caused by multiple devices connected to a common single phase supply, combine. Simple cancellation rules are suggested based on probabilistic integrals and Monte Carlo simulation. The analysis is general in that it applies equally to harmonics of all orders (of the fundamental) and to both current sources (generators) and sinks (loads). Formulas for both equal and unequal harmonic magnitudes are presented
Keywords :
Monte Carlo methods; invertors; power supplies to apparatus; power system harmonics; probability; switching circuits; Monte Carlo simulation; cancellation rules; combined switching harmonics; common single phase supply; current sources; equal harmonic magnitudes; generators; loads; multiple devices; multiple grid-connected single-phase inverters; probabilistic integrals; random phase harmonics; sinks; unequal harmonic magnitudes;
fLanguage :
English
Journal_Title :
Generation, Transmission and Distribution, IEE Proceedings-
Publisher :
iet
ISSN :
1350-2360
Type :
jour
DOI :
10.1049/ip-gtd:20010434
Filename :
959676
Link To Document :
بازگشت