• DocumentCode
    1544157
  • Title

    Automation of the ANSI C119.4-1991 connector test

  • Author

    Hutchinson, Ted F.

  • Author_Institution
    3M Electrical Products Lab., Austin, TX, USA
  • Volume
    12
  • Issue
    2
  • fYear
    1997
  • fDate
    4/1/1997 12:00:00 AM
  • Firstpage
    560
  • Lastpage
    564
  • Abstract
    Automation of the ANSI C119.4-1991 connector test has been expensive. The ANSI test requires accelerated aging using AC current. The resistance of each connector must be measured periodically using DC current. These requirements generate the need for two power sources switched in and out by a computer-controlled relay. This relay must have contact current carrying capabilities equal to that of the cable on test. For large conductor sizes this expense becomes formidable. A method of making accurate ohm measurements of the connectors without connecting or disconnecting the conductor is given in this paper. Automation of the test can be established for a minimal investment with the information given. Automation will allow more information to be gathered, which will lead to the connector aging process being better understood and controlled
  • Keywords
    ANSI standards; ageing; automatic testing; electric connectors; electric resistance measurement; life testing; AC current; ANSI C119.4-1991 connector test automation; DC current; accelerated aging; computer-controlled relay; power sources; resistance measurement; Accelerated aging; Automatic testing; Automation; Conductors; Connectors; Contacts; Current measurement; Electrical resistance measurement; Power generation; Relays;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.584322
  • Filename
    584322