Title :
Pollution performance of 110 kV metal oxide arresters
Author :
Chrzan, Krystian ; Pohl, Zbigniew ; Grzybowski, Stan ; Köhler, Wolfgang
Author_Institution :
Dept. of Electr. Eng., Tech. Univ. Wroclaw, Poland
fDate :
4/1/1997 12:00:00 AM
Abstract :
Pollution test results of single-unit 110 kV metal oxide surge arresters with porcelain housing according to the solid layer and salt fog methods are presented. During 6 hours of testing, the internal and external charge and maximum temperature along the varistor column were measured. The formation of single stable dry bands on the housing was often observed especially during salt fog tests. In such cases, the varistor temperature can reach about 70°C. The simple electrical model of the arrester enabling calculations of voltages and currents as a function of arrester and pollution parameters is shown
Keywords :
arresters; charge measurement; electric breakdown; insulation testing; temperature measurement; thermal analysis; varistors; 110 kV; 6 h; 70 C; electrical model; external charge; insulation breakdown testing; internal charge; maximum temperature; metal-oxide surge arresters; pollution performance tests; porcelain housing; salt fog tests; solid layer tests; varistor column; Arresters; Charge measurement; Current measurement; Pollution; Porcelain; Solids; Surges; Temperature; Testing; Varistors;
Journal_Title :
Power Delivery, IEEE Transactions on