• DocumentCode
    1544354
  • Title

    Defective insulators in live working on a 550 kV compact steel lattice tower

  • Author

    Gela, G. ; Kientz, H. ; Fox, H.J., Jr ; Mitchell, J.D. ; Lyons, P.F.

  • Author_Institution
    EPRI Power Delivery Center, Lenox, MA, USA
  • Volume
    12
  • Issue
    2
  • fYear
    1997
  • fDate
    4/1/1997 12:00:00 AM
  • Firstpage
    783
  • Lastpage
    790
  • Abstract
    Research was conducted to determine the minimum number of healthy insulator units needed to ensure worker safety in live working on a compact 550 kV steel lattice tower. A large variety of worksite conditions was investigated. Test results confirm the conservative nature of the CIGRE formula for defective insulator units, and modifications to the formula are suggested. The recommended number of healthy units is 12 in a string of 24 units for the case of live work on the compact 550 kV tower, when the Portable Protective Gap (PPG) is used. Adjustment for altitude should be made above 900 m (3000´)
  • Keywords
    insulators; maintenance engineering; poles and towers; power overhead lines; power transmission lines; safety; steel; 550 kV; EHV; Portable Protective Gap; compact steel lattice tower; defective insulators; live working; worker safety; worksite conditions; Dielectrics and electrical insulation; IEEE members; Lattices; Occupational stress; Poles and towers; Protection; Safety; Steel; Surges; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.584373
  • Filename