Electrical test methods for nonceramic insulators used for live line replacement
Author
Karady, G.G.
Volume
12
Issue
2
fYear
1997
fDate
4/1/1997 12:00:00 AM
Firstpage
965
Lastpage
970
Abstract
The utilities frequently use nonceramic insulators for live line maintenance. These insulators are not always tested electrically during manufacture. Undetected internal failures in an insulator may endanger workers performing live line maintenance on the insulators. The live line maintenance requires careful testing of each insulator before use. For the selection of the most effective test method, insulators were purposely made with internal flaws and then subjected to megger, hot stick, partial discharge and RIV tests as well as measurement of the total and surface component of leakage current, together with surface heating measurement. The most sensitive method is the RIV test, which identified 6 insulators with flaws. The partial discharge and hot stick tests found 4 insulators with embedded wire. From a practical point of view, the modified hot stick test seems to be suitable for field test of the insulators
Keywords
charge measurement; insulator testing; leakage currents; maintenance engineering; partial discharges; temperature measurement; RIV test; electrical test methods; embedded wire; flaw detection; hot stick test; internal flaws; leakage current surface component; live line maintenance; live line replacement; megger test; nonceramic insulators; partial discharge test; surface heating measurement; undetected internal failures; Cable insulation; Current measurement; Dielectrics and electrical insulation; Heating; Insulator testing; Leakage current; Manufacturing; Partial discharge measurement; Partial discharges; Surface discharges;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.584421
Filename
584421
Link To Document