DocumentCode :
1545586
Title :
Reduced substation models for generalized state estimation
Author :
Expósito, Antonio Gómez ; De La Villa Jaén, Antonio
Author_Institution :
Dept. of Electr. Eng., Seville Univ., Spain
Volume :
16
Issue :
4
fYear :
2001
fDate :
11/1/2001 12:00:00 AM
Firstpage :
839
Lastpage :
846
Abstract :
This paper deals with the problem of including detailed substation models in state estimators so that topological errors and/or bad internal data can be detected and identified. Instead of analyzing constraints and state variables related to individual circuit breakers, the whole substation is reconsidered in the light of topological properties, leading to a model where zero-injection constraints are not explicitly handled. In addition, it is shown how, if the new state variables are selected keeping certain rules in mind, the resulting constraints can be easily transformed into equivalent constraints, many of which appear as critical. This allows a reduced model to be used without losing any capability to perform error analysis
Keywords :
circuit breakers; power system state estimation; substations; bad internal data; circuit breakers; equivalent constraints; error analysis performance; generalized state estimation; linearly independent equality contraints; reduced substation models; state variables; topological errors; topological properties; zero-injection constraints; Circuit breakers; Circuit testing; Circuit topology; Convergence; Data analysis; Error analysis; Power system measurements; Power system modeling; State estimation; Substations;
fLanguage :
English
Journal_Title :
Power Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8950
Type :
jour
DOI :
10.1109/59.962435
Filename :
962435