DocumentCode
1547918
Title
Cumulant Method Equivalent Load Curve Calculation Performance for Small Generation Systems
Author
Smith, R.A. ; Shultz, R.D. ; Sweet, T.M.
Author_Institution
Electrical Engineering Dept., University of Illinois, Urbana, IL
Issue
5
fYear
1983
fDate
5/1/1983 12:00:00 AM
Firstpage
45
Lastpage
46
Abstract
The purpose of this paper is to present computational experience of the cumulant method of generation system production cost calculations. This method has been recommended for use in analysis of generation systems with individual generators sized at less than 10% of total generation capacity and with forced outage rates greater than 10% However, smaller utilities have generation systems that do not have these characteristics This phenomenon can cause errors in the production cost results using the cumulant method. This paper examines and compares equivalent load curves calculated by the cumulant method and conventional convolution. Recommendations are made on generator state models and the number of cumulants used in the calculations in order to reduce cumulant method errors. The results of these recommendations show that production cost calculations using the cumulant method are entirely acceptable for screening generation expansion plans.
Keywords
Constraint theory; DC generators; Power generation; Predictive models; Pricing; Space cooling; Space heating; Temperature dependence; Temperature distribution; Thermodynamics;
fLanguage
English
Journal_Title
Power Engineering Review, IEEE
Publisher
ieee
ISSN
0272-1724
Type
jour
DOI
10.1109/MPER.1983.5519167
Filename
5519167
Link To Document