• DocumentCode
    1553193
  • Title

    Investigation of a unified power flow controller

  • Author

    Makombe, T. ; Jenkins, N.

  • Author_Institution
    Centre for Electr. Energy, Univ. of Manchester Inst. of Sci. & Technol., UK
  • Volume
    146
  • Issue
    4
  • fYear
    1999
  • fDate
    7/1/1999 12:00:00 AM
  • Firstpage
    400
  • Lastpage
    408
  • Abstract
    Power flow in an AC transmission system depends on three basic parameters: transmission line impedance, voltage magnitude and phase angle. Maximum utilisation of the power system can be ensured by the control of these parameters in real-time. It is shown experimentally that a unified power flow controller (UPFC) can control each of the parameters either selectively or simultaneously in appropriate combinations. It is also shown that a UPFC can control independently the real and reactive power flow in a transmission circuit. Results from computer simulations and a hardware laboratory model are presented
  • Keywords
    load flow control; power transmission control; reactive power control; AC transmission system; UPFC; computer simulations; hardware laboratory model; phase angle; power flow; reactive power flow; real power flow; real-time control; transmission line impedance; unified power flow controller; voltage magnitude;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings-
  • Publisher
    iet
  • ISSN
    1350-2360
  • Type

    jour

  • DOI
    10.1049/ip-gtd:19990037
  • Filename