Partial discharge screening test for internal voids and delaminations in stator coils and bars
Author
McDermid, W. ; Bromley, J.C.
Author_Institution
Manitoba Hydro, Winnipeg, Man., Canada
Volume
14
Issue
3
fYear
1999
fDate
9/1/1999 12:00:00 AM
Firstpage
292
Lastpage
297
Abstract
Beginning in 1989 a partial discharge screening test was applied to stator coils and bars for which the measuring frequency bandwidth was approximately 8 MHz to 100 MHz. In this frequency range, the measurement is more sensitive to partial discharges in internal voids and delaminations than is the case for discharges associated with surface coatings. Recently changes have been made to the test circuit which have improved the repeatability of the measurement. Selection of the operating voltage for particular stator coils and bars based on their partial discharge screening test results may reduce the risk of future problems with the winding
Keywords
hydroelectric generators; insulation testing; machine insulation; machine testing; partial discharge measurement; stators; voids (solid); 8 to 100 MHz; delaminations; frequency range; hydrogenerator insulation breakdown testing; internal voids; measuring frequency bandwidth; operating voltage selection; partial discharge screening test; repeatability; stator bars; stator coils; test circuit; winding; Bandwidth; Bars; Circuit testing; Coils; Delamination; Frequency measurement; Partial discharge measurement; Partial discharges; Stators; Surface discharges;
fLanguage
English
Journal_Title
Energy Conversion, IEEE Transactions on
Publisher
ieee
ISSN
0885-8969
Type
jour
DOI
10.1109/60.790872
Filename
790872
Link To Document