DocumentCode
1555202
Title
Study of a circuit-breaker arc with self-generated flow. III. The post-arc phase
Author
Gleizes, A. ; Mitiche, M. ; Van Doan, Pham
Author_Institution
Univ. Paul Sabatier, Toulouse, France
Volume
19
Issue
1
fYear
1991
fDate
2/1/1991 12:00:00 AM
Firstpage
12
Lastpage
19
Abstract
For pt.II see ibid., vol.16, p.615-22, 1988. The third part of this study of a circuit-breaker arc with self-generated flow concerns the model of the post-arc phase. The greater interruption capability of SF6 compared to N2, already suggested in pt.II, is confirmed by the following results: amplitude and duration of the postarc current are much lower in SF6 and the maximum value of the rate of rise of recovery voltage is about three times higher in SF6 than in N2. The model also predicts the existence of a plateau in post-arc current variation and the original behavior of this type of circuit-breaker: interrupting efficiency increases with the current peak in the initial phase
Keywords
circuit-breaking arcs; sulphur compounds; N2; SF6; circuit-breaker arc; current amplitude; current duration; interrupting efficiency; model; post-arc phase; recovery voltage; self-generated flow; Absorption; Circuit breakers; Circuit testing; Energy exchange; Equations; Mathematical model; Nitrogen; Predictive models; Sulfur hexafluoride; Voltage;
fLanguage
English
Journal_Title
Plasma Science, IEEE Transactions on
Publisher
ieee
ISSN
0093-3813
Type
jour
DOI
10.1109/27.62361
Filename
62361
Link To Document