DocumentCode
1555685
Title
Elimination of Closing Resistors for Breakers in 1000-kV UHV System by Surge Arresters
Author
He, Jinliang ; Li, Chen ; Hu, Jun ; Zeng, Rong ; Yuan, Jun
Author_Institution
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
Volume
27
Issue
4
fYear
2012
Firstpage
2168
Lastpage
2175
Abstract
Closing resistors for breakers are used to suppress switching overvoltages, but their shortcomings make it a long-standing goal to eliminate closing resistors. In this paper, different arresters are evaluated as alternative measures to eliminate closing resistors in 1000-kV ultra-high voltage (UHV) systems. Two kinds of arresters with lower residual voltage are introduced to suppress switching overvoltages. The performance of these arresters under different operation conditions is also analyzed to ensure the safety of arresters. It is shown that closing resistors in UHV systems can be eliminated after applying proper arresters and adopting certain distributing measures.
Keywords
arresters; circuit breakers; resistors; UHV system; breakers; closing resistors; long-standing goal; lower residual voltage; operation conditions; suppress switching overvoltages; surge arresters; ultra-high voltage systems; voltage 1000 kV; Absorption; Arresters; Energy management; Resistors; Surges; Thermal stability; Transmission line measurements; Voltage control; Absorbed energy; closing resistors; high applied voltage ratio arrester; low residual voltage arrester; switching overvoltage; ultra-high voltage (UHV) system;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2012.2202293
Filename
6236276
Link To Document