• DocumentCode
    1555706
  • Title

    500-kV EHV Bundle Conductors´ Corona Onset Voltage Calculation and Analysis in Corona Cage at Different Altitudes

  • Author

    Liu, Yun-Peng ; You, Shao-Hua ; Lü, Fang-Cheng ; Wan, Qi-Fa ; Bian, Xing-Ming ; Wang, Li-Ming

  • Author_Institution
    Hebei Provincial Key Lab. of Power Transm. Equip. Security Defense, North China Electr. Power Univ., Baoding, China
  • Volume
    27
  • Issue
    4
  • fYear
    2012
  • Firstpage
    2090
  • Lastpage
    2097
  • Abstract
    In order to research an altitude´s effect on corona onset voltage of bundle conductors in a corona cage, a calculation model was established, and corresponding test proceeded. The charge simulation method was adopted to calculate space electric-ήeld strength. According to self-sustained discharge criterion in a severe nonuniform electric ήeld, and variation of altitude, the corona onset voltage calculation model of bundle conductors in a corona cage was established. The corona onset voltages of bundle conductors, which were used in the 500-kV extremely high voltage transmission line, were tested at different altitude locations, as Wuhan 19 m, Xining 2261 m, Golmud 2829 m, and Nachitai 3800 m. Corona onset voltages of 4 × LGJ - 0400/5 and 4 × LGJ - 300/25 were obtained. The corona onset voltage curves at different altitude, bundle spacing, and bundle numbers were obtained. The analysis shows that the model can be used to provide accurate values of corona onset voltage for bundled stranded conductors in the corona cage at various altitudes. With bundle spacing from 350 to 500 mm, the corona onset voltage decreases as bundle spacing increases, and the onset voltage increases as the bundle number increases. As altitude increases every 1000 m, the corona onset voltage of bundle conductors decreases by about 8.5%.
  • Keywords
    conductors (electric); corona; Golmud 2829; Nachitai 3800; Wuhan 19; Xining 2261; altitude locations; altitudes; bundle conductors; charge simulation method; corona cage; corona onset voltage analysis; corona onset voltage calculation; corona onset voltages; high voltage transmission line; nonuniform electric field; space electric-field strength; voltage 500 kV; Attitude control; Conductors; Corona; Current measurement; Discharges; Ionization; Voltage measurement; Altitude; bundle conductors; corona cage; corona onset voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2012.2202694
  • Filename
    6236281