DocumentCode :
1556155
Title :
Adaptive non-communication protection for power lines BO scheme 1-The delayed operation approach
Author :
Bo, Zhiqian Q.
Author_Institution :
Alstom T&D Protection & Control Ltd, Stafford, UK
Volume :
17
Issue :
1
fYear :
2002
fDate :
1/1/2002 12:00:00 AM
Firstpage :
85
Lastpage :
91
Abstract :
This paper proposes a new technique in power line protection, the "adaptive non-communication protection". In this technique, protection relays make operate or restraint decisions, adapting to system and fault conditions, without the need for communication links. Operation without communication links to signal the remote end relay is achieved by the detection and identification of the operation of the circuit breaker at the remote end of the protected line section. An algorithm based on symmetric components is proposed to detect and identify the balance condition of the power system during the fault. The paper is focused on one of the three protection schemes based on the new technique, the delayed operation scheme. Simulation studies carried out for various power systems and fault conditions have demonstrated its feasibility
Keywords :
adaptive control; circuit breakers; power transmission control; power transmission faults; power transmission lines; power transmission protection; BO protection; adaptive noncommunication power line protection; circuit breaker; delayed operation approach; fault conditions; operate decisions; protection relays; protection schemes; restraint decisions; simulation studies; symmetric components algorithm; Circuit breakers; Circuit faults; Electrical fault detection; Fault detection; Power system faults; Power system protection; Power system relaying; Power system simulation; Protective relaying; Signal processing;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.974192
Filename :
974192
Link To Document :
بازگشت