DocumentCode :
1557555
Title :
A New Digital Distance Relaying Scheme for Compensation of High-Resistance Faults on Transmission Line
Author :
Makwana, Vijay H. ; Bhalja, Bhavesh R.
Author_Institution :
Dept. of Electr. Eng., G.H. Patel Coll. of Eng. & Technol., Vallabh Vidyanagar, India
Volume :
27
Issue :
4
fYear :
2012
Firstpage :
2133
Lastpage :
2140
Abstract :
Performance of the conventional ground distance relaying scheme is adversely affected by different types of ground faults, such as single line to ground, double line to ground, and simultaneous open conductor and ground. This effect is more pronounced due to the considerable value of fault resistance and direction and magnitude of power flow. The work presented in this paper addresses the aforementioned problems encountered by the conventional ground distance relaying scheme when protecting doubly fed transmission lines. Further, a new digital distance relaying scheme is proposed which compensates the errors produced by the conventional ground distance relaying scheme using local-end data only. The detailed analysis of the apparent impedance as seen from the relaying point by the conventional ground distance relaying scheme and the proposed scheme during different types of ground faults is also presented in this paper. The feasibility of the proposed scheme has been tested using MATLAB/SIMULINK software. The simulation results demonstrate the effectiveness of the proposed scheme since it provides accuracy on the order of 98%.
Keywords :
earthing; power transmission faults; power transmission lines; power transmission protection; relay protection; Matlab-Simulink software; conventional ground distance relaying scheme; digital distance relaying scheme; double-line-to-ground fault; doubly-fed transmission line protection; fault resistance; high-resistance fault compensation; local-end data; power flow direction; power flow magnitude; simultaneous open-conductor-and-ground fault; single-line-to-ground fault; Circuit faults; Electrical resistance measurement; Fault location; Impedance; Power transmission lines; Resistance; Transmission line measurements; Doubly fed transmission line; ground distance relay; high resistance fault; simultaneous open conductor and ground fault; single-line-to-ground fault;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2012.2202922
Filename :
6239625
Link To Document :
بازگشت