    A study of zero-sequence current induced in a cable system

  • Author

    Nakanishi, H. ; Inoguchi, H. ; Hashimoto, I. ; Ito, Y. ; Takehana, H. ; Nagaoka, N. ; Ametani, A.

  • Author_Institution
    Kansai Electric Power Co., Osaka, Japan
  • Volume
    6
  • Issue
    4
  • fYear
    1991
  • fDate
    10/1/1991 12:00:00 AM
  • Firstpage
    1352
  • Lastpage
    1358
  • Abstract
    Large zero-sequence currents found in an actual crossbonded cable system led to a study of their causes and a solution to the problem. Measured values were compared to calculated results by the BPA-EMTP circuit analysis program. It was found that the zero-sequence currents were circulating between different circuits in the cable system and that they were being generated by the induction between phases in the same cable route. It was determined that the zero-sequence currents could be greatly reduced in a twin circuit (six phases) by symmetrical configuration of the cables. However, in a four-circuit system, no significant reduction could be achieved even by the symmetrical configuration
  • Keywords
    distribution networks; power cables; power engineering computing; BPA-EMTP circuit analysis program; cable system; crossbonded cable system; four-circuit system; induction; symmetrical cable configuration; twin circuit; zero-sequence current; Circuits; Conductors; Current measurement; EMTP; Power cables; Power measurement; Power transmission lines; Substations; Transformers; Underground power cables;