• DocumentCode
    1558848
  • Title

    Analysis of surges measured at 550 kV substations

  • Author

    Okabe, S. ; Kan, M. ; Kouno, T.

  • Author_Institution
    Tokyo Electric Power Co. Inc., Tokyo, Japan
  • Volume
    6
  • Issue
    4
  • fYear
    1991
  • fDate
    10/1/1991 12:00:00 AM
  • Firstpage
    1462
  • Lastpage
    1468
  • Abstract
    An automatic measuring system was developed for measuring overvoltages, and it was applied to 550 kV power stations and substations in service. This system has been in operation since June 1987, and 176 records have been successfully obtained. Induced-lightning surges, back-flashover surges due to lightning, circuit-breaker-closing surges, and gas-insulated-substation (GIS)-disconnector-switching surges were recorded. Using simple EMTP analysis, the authors were able to reproduce the fundamental characteristics of the measured waveforms. The authors report on such measured data and on the results of data analysis
  • Keywords
    circuit breakers; flashover; lightning; overvoltage; substations; surges; switching; voltage measurement; 550 kV; EMTP analysis; GIS; automatic measuring system; back-flashover surges; circuit-breaker-closing surges; disconnector-switching surges; gas-insulated-substation; overvoltage measurement; power stations; substations; surge measurement; Bandwidth; Circuits; EMTP; Frequency measurement; Insulation; Lightning; Power measurement; Substations; Surges; Voltage control;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.97678
  • Filename
    97678