    Field distribution on an HVDC wall bushing during laboratory rain tests

  • Author

    Lampe, W. ; Wikström, D. ; Jacobson, B.

  • Author_Institution
    Swedish Transmission Res. Inst., Ludvika, Sweden
  • Volume
    6
  • Issue
    4
  • fYear
    1991
  • fDate
    10/1/1991 12:00:00 AM
  • Firstpage
    1531
  • Lastpage
    1540
  • Abstract
    An efficient countermeasure to suppress flashovers across high-voltage DC (HVDC) wall bushings is to make their surfaces hydrophobic. The measured electric fields along such a bushing under different environmental conditions are reported. A significantly reduced radial field strength has been found for the hydrophobic bushing. Moreover, the total field strength distribution becomes almost independent of the prevailing dry zone. The flashover voltage for bushings with a hydrophobic surface is therefore significantly increased
  • Keywords
    DC power transmission; bushings; electric field measurement; flashover; HVDC wall bushing; electric field measurement; field strength distribution; flashovers; hydrophobic bushing; laboratory rain tests; radial field strength; Flashover; HVDC transmission; Insulators; Laboratories; Pollution measurement; Probes; Rain; Testing; Valves; Voltage;