Field distribution on an HVDC wall bushing during laboratory rain tests
Author
Lampe, W. ; Wikström, D. ; Jacobson, B.
Author_Institution
Swedish Transmission Res. Inst., Ludvika, Sweden
Volume
6
Issue
4
fYear
1991
fDate
10/1/1991 12:00:00 AM
Firstpage
1531
Lastpage
1540
Abstract
An efficient countermeasure to suppress flashovers across high-voltage DC (HVDC) wall bushings is to make their surfaces hydrophobic. The measured electric fields along such a bushing under different environmental conditions are reported. A significantly reduced radial field strength has been found for the hydrophobic bushing. Moreover, the total field strength distribution becomes almost independent of the prevailing dry zone. The flashover voltage for bushings with a hydrophobic surface is therefore significantly increased
Keywords
DC power transmission; bushings; electric field measurement; flashover; HVDC wall bushing; electric field measurement; field strength distribution; flashovers; hydrophobic bushing; laboratory rain tests; radial field strength; Flashover; HVDC transmission; Insulators; Laboratories; Pollution measurement; Probes; Rain; Testing; Valves; Voltage;