DocumentCode :
1558950
Title :
Impact of utility switched capacitors on customer systems. II. Adjustable-speed drive concerns
Author :
McGranaghan, M.F. ; Grebe, T.E. ; Hensley, G. ; Singh, T. ; Samotyj, M.
Author_Institution :
Electrotek Concepts Inc., Knoxville, TN, USA
Volume :
6
Issue :
4
fYear :
1991
fDate :
10/1/1991 12:00:00 AM
Firstpage :
1623
Lastpage :
1628
Abstract :
The authors investigate nuisance tripping of adjustable-speed drives caused by capacitor switching on the utility distribution system. The authors discuss the basic phenomena and then present the results of sensitivity analysis simulations performed to explore the various parameters which can affect the problem. The important parameters include the source strength at the switched capacitor, the switched capacitor bank size, the customer step down transformer size, the drive characteristics, and system loading
Keywords :
distribution networks; power capacitors; switching; variable speed drives; adjustable-speed drives; capacitor switching; customer step down transformer; distribution system; drive characteristics; nuisance tripping; sensitivity analysis; switched capacitor bank; system loading; Analytical models; Inductance; Inductors; Low voltage; Performance evaluation; Power capacitors; Power quality; Pulse width modulation inverters; Sensitivity analysis; Variable speed drives;