DocumentCode :
1558968
Title :
Frequency response analysis and modeling of measurement transformers under distorted current and voltage supply
Author :
Samesima, M.I. ; de Oliveira, J.C. ; Dias, E.M.
Author_Institution :
Fed. Univ. of Uberlandia, Brazil
Volume :
6
Issue :
4
fYear :
1991
fDate :
10/1/1991 12:00:00 AM
Firstpage :
1762
Lastpage :
1768
Abstract :
The time and frequency response of current and potential transformers (CTs and PTs) operating under fundamental frequency conditions are well known. However, in the presence of harmonic frequencies, these transformers can exhibit significant errors. The authors present CT and PT comprehensive frequency domain equivalent circuits which, in addition to previous study features, include the hysteresis and eddy current effects. Furthermore, a practical approach which calculates the stray capacitances is proposed. By comparing theoretical and practical results the importance of considering parameters which are usually ignored in such studies is highlighted
Keywords :
current transformers; eddy currents; equivalent circuits; frequency response; frequency-domain analysis; harmonics; magnetic hysteresis; potential transformers; current transformers; distorted current supply; distorted voltage supply; eddy current effects; frequency domain equivalent circuits; frequency response; harmonic frequencies; hysteresis effects; measurement transformers; potential transformers; stray capacitances; time response; Capacitance; Circuit testing; Current measurement; Current transformers; Distortion measurement; Equivalent circuits; Frequency domain analysis; Frequency measurement; Frequency response; Voltage transformers;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.97718