  • Abstract
    This paper has proposed a new fault location method for three terminal transmission lines. Once a fault occurs in a transmission line, high frequency transient components through travelling of the waves are appeared in all terminals. In this paper, S-transform is employed to detect the arrival time of these waves to terminals. For simulating various conditions, ATP-EMTP software and to process the proposed fault location method MATLAB software are used. The results have shown the good performance of the algorithm in different conditions.
  • Keywords
    fault location; power transmission faults; power transmission lines; power transmission protection; transforms; ATP-EMTP software; MATLAB software; S-transform; fault location method; high frequency transient components; three terminal transmission lines; Circuit faults; Fault location; Power transmission lines; Resistance; Synchronization; Transforms; fault location; protection; three terminal power transmission lines;