    AC impedance testing for valve regulated cells

  • Author

    Markle, Gary J.

  • Author_Institution
    AVO Biddle Instruments, Blue Bell, PA, USA
  • fYear
    1992
  • Firstpage
    212
  • Lastpage
    217
  • Abstract
    The author describes how the AC impedance of a valve regulated lead acid (VRLA) cell can be an indicator of the condition of the standby battery system. Used in conjunction with load cycle testing impedance testing identifies cells requiring replacement, reduces performance testing, and reinforces confidence in the battery system. Test results are presented which confirm the impedance test as the first true diagnostic test for VRLA cells. The condition of VRLA battery systems is examined, common failure modes are identified, test regimens are described, and actual test data are presented
  • Keywords
    electric impedance; failure analysis; lead; load (electric); reliability; secondary cells; testing; AC impedance testing; Pb acid secondary cells; diagnosis; failure modes; load cycle testing; performance testing; reliability; standby battery system; valve regulated cells; Batteries; Hydrogen; Impedance; Inspection; Instruments; Manufacturing; System testing; Temperature; Valves; Voltage;