  • Abstract
    Issues of safety and service life in the use of standby batteries in telecommunication power installations are considered from the perspectives of hydrogen gas emission and thermal runaway. The relationship between the safety and the life issues related to the control of float current and temperature is discussed. Recommendations for such control are proposed. Float voltage compensation reduces the prevailing float current level, and partially compensates for the adverse effects of temperature increases
  • Keywords
    emergency power supply; safety; secondary cells; telecommunication equipment; float current control; float current level; float voltage compensation; high energy density battery; hydrogen gas emission; safety; service life; standby batteries; telecommunication power installations; temperature control; thermal runaway; Battery management systems; Energy management; Hydrogen; Safety devices; Telecommunication control; Temperature sensors; Thermal management; Thermal resistance; Valves; Voltage;