DocumentCode
1576585
Title
Thermal management of high energy density battery equipments
Author
Harrison, A.I.
Author_Institution
Chloride Industrial Batteries Ltd., Manchester, UK
fYear
1992
Firstpage
28
Lastpage
34
Abstract
Issues of safety and service life in the use of standby batteries in telecommunication power installations are considered from the perspectives of hydrogen gas emission and thermal runaway. The relationship between the safety and the life issues related to the control of float current and temperature is discussed. Recommendations for such control are proposed. Float voltage compensation reduces the prevailing float current level, and partially compensates for the adverse effects of temperature increases
Keywords
emergency power supply; safety; secondary cells; telecommunication equipment; float current control; float current level; float voltage compensation; high energy density battery; hydrogen gas emission; safety; service life; standby batteries; telecommunication power installations; temperature control; thermal runaway; Battery management systems; Energy management; Hydrogen; Safety devices; Telecommunication control; Temperature sensors; Thermal management; Thermal resistance; Valves; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Telecommunications Energy Conference, 1992. INTELEC '92., 14th International
Conference_Location
Washington, DC
Print_ISBN
0-7803-0779-8
Type
conf
DOI
10.1109/INTLEC.1992.268467
Filename
268467