    Grid code requirements concerning connection and operation of wind turbines in Germany

  • Author

    Erlich, I. ; Bachmann, U.

  • Author_Institution
    Dept. of Power Syst., Duisburg Univ., Germany
  • fYear
    2005
  • Firstpage
    1253
  • Abstract
    This paper discusses issues of German grid codes relating to wind turbines. With the high utilization of wind power a simultaneous loss of several thousand MW wind generation became a realistic scenario in the German power system. Therefore, the main requirements concern the fault ride through capability of wind turbines. Accordingly, disconnection of wind turbines and wind farms above 15 % nominal voltage at the grid connection nodes is not allowed. Besides, following network faults wind turbines have to supply a definite reactive current depending on the instantaneous voltage. Furthermore, they must return quickly to normal operation. The frequency range wind turbines have to tolerate is about 47.5-51.5 Hz. According to the wishes of German transmission grid operators, large wind farms have to be treated in the future like conventional power plants.
  • Keywords
    power generation faults; power grids; wind turbines; German transmission grid operators; German wind turbines; grid code requirements; instantaneous voltage; network faults; reactive current; wind farms; wind power utilization; Gold; Investments; Power generation; Renewable energy resources; Voltage; Wind energy; Wind energy generation; Wind farms; Wind power generation; Wind turbines;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Society General Meeting, 2005. IEEE
  • Print_ISBN
    0-7803-9157-8
  • Type

    conf

  • DOI
    10.1109/PES.2005.1489534
  • Filename
    1489534