Grid code requirements concerning connection and operation of wind turbines in Germany
Author
Erlich, I. ; Bachmann, U.
Author_Institution
Dept. of Power Syst., Duisburg Univ., Germany
fYear
2005
Firstpage
1253
Abstract
This paper discusses issues of German grid codes relating to wind turbines. With the high utilization of wind power a simultaneous loss of several thousand MW wind generation became a realistic scenario in the German power system. Therefore, the main requirements concern the fault ride through capability of wind turbines. Accordingly, disconnection of wind turbines and wind farms above 15 % nominal voltage at the grid connection nodes is not allowed. Besides, following network faults wind turbines have to supply a definite reactive current depending on the instantaneous voltage. Furthermore, they must return quickly to normal operation. The frequency range wind turbines have to tolerate is about 47.5-51.5 Hz. According to the wishes of German transmission grid operators, large wind farms have to be treated in the future like conventional power plants.
Keywords
power generation faults; power grids; wind turbines; German transmission grid operators; German wind turbines; grid code requirements; instantaneous voltage; network faults; reactive current; wind farms; wind power utilization; Gold; Investments; Power generation; Renewable energy resources; Voltage; Wind energy; Wind energy generation; Wind farms; Wind power generation; Wind turbines;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Society General Meeting, 2005. IEEE
Print_ISBN
0-7803-9157-8
Type
conf
DOI
10.1109/PES.2005.1489534
Filename
1489534
Link To Document