DocumentCode
1583869
Title
Research of applying hybrid active filter to compensate harmonics in DC-link of the inverter
Author
Wang, Ping ; Song, Liangyu ; Sun, Yugeng ; Sun, Xu
Author_Institution
Dept. of Electr. Eng. & Autom., Tianjin Univ., China
Volume
6
fYear
2004
Firstpage
5116
Abstract
A shunt hybrid active power filter (APF) as harmonic generator taken to the DC link of the inverter eliminates harmonic wave generated by the inverter in this paper. Control is mixed by fuzzy logic control and hysteresis control and uses the digital signal processor. The value of DC-link inductance in the APF kept invariableness by this method, which made APF generate the harmonics current compensated accurately. In this system, it allows to test and validate easily different current or DC voltage control. The system is investigated analytically as well as experimentally. The obtained results are presented and discussed to prove the effectiveness of the design and control strategy.
Keywords
active filters; fuzzy control; harmonic generation; hysteresis; invertors; machine control; power harmonic filters; DC link inverter; digital signal processor; fuzzy logic control; harmonic generator; harmonic wave; hysteresis control; shunt hybrid active power filter; Active filters; DC generators; Digital signal processors; Fuzzy logic; Hybrid power systems; Hysteresis; Inverters; Power generation; Power harmonic filters; Power system harmonics;
fLanguage
English
Publisher
ieee
Conference_Titel
Intelligent Control and Automation, 2004. WCICA 2004. Fifth World Congress on
Print_ISBN
0-7803-8273-0
Type
conf
DOI
10.1109/WCICA.2004.1343694
Filename
1343694