            Abstract : 
This paper investigates the effect of a nonuniform distribution of a conductive surface layer along the length of a 275 kV cap and pin insulator string. The worst case is when one or two clean discs are inserted in a polluted string. A high electric field then exists across the clean discs, distorting the field to such an extent that localised flashover occurs across the clean discs
         
        
            Keywords : 
insulator contamination; 275 kV; cap and pin insulator string; clean discs insertion; conductive surface layer; electric field distortion; high electric field; localised flashover; nonuniform distribution; polluted AC insulator string;
         
        
        
        