  • Abstract
    An important issue in uninterruptible power systems is recharging of the storage battery after line interruptions. Recharging may become marginal if the load absorbs constant power, and if the rectifiers feature a constant-current limit. It is shown that in the recharging mode the constant-power rectifiers perform better than their constant-current counterparts
  • Keywords
    optimisation; rectifying circuits; redundancy; reliability; secondary cells; uninterruptible power supplies; DC power plants; backup batteries; constant-current limit; constant-power loads; line interruptions; rectifiers; redundancy; reliability optimisation; storage battery recharging; uninterruptible power systems; Batteries; Electric breakdown; Electronic equipment; Low voltage; Power generation; Power generation economics; Power system economics; Power system reliability; Rectifiers; Uninterruptible power systems;